Troubleshooting and fault elimination, 8troubleshooting and fault elimination – Lenze 931W User Manual

Page 45

Advertising
background image

Troubleshooting and fault elimination

Fault elimination for general errors

8

45

GHB 13.0002-EN 3.1

8

Troubleshooting and fault elimination

8.1

Fault elimination for general errors

Error

Cause

Remedy

No communication with drive possible

Supply voltage error

Check connections and supply of the

control and power voltage.

Communication error or defective RS232

communication cable

Check setting of the COM port in Fluxx

operating software

Check connection of the serial RS232 cable

Replace RS232 cable (cable defect)

Digital IOs do not function

24 V control voltage not connected

Connect 24V control voltage / check

control voltage

Local CAN interface or function module

does not function

24 V control voltage not connected (LED

on application box/function module is not

blinking)

Connect 24V control voltage / check

control voltage

Check 4-pole communication cable

between drive and application box

Communication error or defective

communication cable

Replace 4-pole communication cable

between drive and application box

Wiring error

Check of the connection of the digital IOs

Drive travels with maximum speed only

Resolver error or connection error in the

motor cable

Carry out resolver position adjustment

Select the option ”Resolver direction

inversion” in the ”Service” tab

Exchange of 2 phases of the connection

(e. g. ”V/U/W” instead of ”U/V/W”)

Fieldbus has parameter change rights

A higher-level control (e. g. Profibus S7)

has the access authorisations to the drive

Return parameter change rights to the

drive

Separation of the guiding from the bus by

means of the ”Quick stop” button in the

Fluxx on the ”Status” tab (caution: drive

stops, bus system is deprived of control

change rights)

Communication loss when travel tasks are

started

Power supply (specifically for DC drives) is

dimensioned too low.

Use voltage supply with higher output

power

Check mains supply with regard to voltage

dips