Troubleshooting and fault elimination – Lenze 931W User Manual

Page 46

Advertising
background image

Troubleshooting and fault elimination

Fault elimination for known error message (see Fluxx, ”Status” tab)

8

46

GHB 13.0002-EN 3.1

8.2

Fault elimination for known error message (see Fluxx, ”Status” tab)

Error message

Cause

Remedy

DC-bus voltage under-run

DC-bus voltage too low

Check supply voltage.

For DC supply voltages where the DC

source features a dynamic that is too high,

or where it is too limited due to the

maximum current, the maximum torque

and the accelerations have to be reduced

Brake voltage beyond the tolerance range Supply voltage of the brake beyond the

tolerance range

The brake voltage is displayed in the

”Status” tab under ”Brake voltage”

Check setting in the ”Service”

”Brake/voltage range” tab (setting range

18…32V).

Observe the correct polarity of the supply

voltage!

Motor temperature exceeded

Evaluation of thermal detector has

actuated

Motor temperature too high

Incorrect or no thermal detector (931W)

Incorrect values in the ”Motor

temperature, speed and position value”

field: feedback connection between motor

and inverter interrrupted.

Electronic temperature exceeded

Temperature of the electronics too high,

cooling not sufficient, utilisation of the

electronics too high

Check ambient conditions of the

electronics (T

ambient

<40°C ?)

Clean heatsink

Check mounting clearances (50 mm to all

sides)

Remove further heat sources near the

drive

Reduce load of the drive (reduce

accelerations, reduce max. torque)

Carry out resolver position adjustment

DC-bus voltage exceeded

DC-bus voltage exceeded, braking energy

too high

Check braking accelerations and

slowing-down process, and, if required,

reduce braking accelerations

At 24 V/42 V DC-power supply: use

feedback-supplying power supply unit

Quick stop

A quick stop has been effected

Check cause (digital input, bus system

control,…)

Eliminate error cause, acknowledge error

Drive not referenced

Drive not referenced / reference run has to

be carried out

For positioning: carry out reference run

Select the following setting for speed,

following error or torque control in the

”Referencing” tab to avoid reference run:

– Reference type ”none”

– Reference start: power up

– Absolute resolver position: -1

Motor current exceeded

Motor is defective (earth fault or phase

leakage), output stage is short-circuited

Output stage and / or motor of the drive is

defective, return drive to manufacturer

Travel data set not executable

Settings in travel data set not conflict-free Check of the settings in the ”Travel data

set” tab

Check of the software limit switch

(”System” tab, use software limit switch

for positioning only!

Check on whether the positioning target is

beyond the software limit switches