Dimensioning, Important notes, 5dimensioning – Lenze EMB9352−C User Manual
Page 76: Stop
Dimensioning
Important notes
5
l
76
EDBMB935X DE/EN/FR 13.0
5
Dimensioning
5.1
Important notes
(
Stop!
Thermal overload of brake chopper EMB9352 or of the brake
resistor.
If the value falls below the brake resistance R
B,min
or if the
maximum running time of the brake chopper / brake resistor is
exceeded, the components will be overloaded.
Possible consequences:
ƒ
The components fail.
Protective measures:
ƒ
Always implement the temperature monitoring of the brake
resistor into the emergency stop chain.
ƒ
Please observe the running time t
on
and dead time t
off
of the
brake resistor and the brake chopper.
ƒ
Calculate the generated braking energy of the application for
brake resistances <R
B,lim
. (
¶ 79)
– Connect the brake chopper in parallel if the maximum values
of the brake chopper are exceeded.
EMB9352
Dimensioning steps
U
ch
= 375 V
U
ch
= 725 V
U
ch
= 765 V
R
B,lim
= 27
W R
B,lim
= 54
W
Brake
resistance R
B
<27
W
<54
W
1. Calculate running time and dead time. (
^
– Condition "t
on
+ t
off
= 3 s" must be observed.
2. Dimension brake chopper and brake resistor .
(
^
³27 W
³54 W
1. Calculate running time and dead time. (
^
– The technical data of the brake resistor must be
observed.