Electrical installation

General requirements

Power connections

7

l

97

EDBMB935X DE/EN/FR 13.0

7.3

General requirements

Preparation

ƒ

Remove cover of the power connections.

ƒ

Remove cover of the control connections.

7.3.1

Power connections

ƒ

The data regarding cable cross−sections and fuses are recommendations
and refer to the use:

In control cabinets and machines

Installation in the cable duct

Maximum ambient temperature +40 °C

ƒ

The cables between the braking unit and the controller may not exceed a
length of 2 m.

For cable lengths

£ 0.5 m you can use unshielded single cores.

ƒ

If an interference suppression of the drive system is required, the cables
have to be shielded

Always apply the shield on both sides.

ƒ

It is the user’s responsibility to take further standards (e. g.: VDE 0113,
VDE 0289, etc.) into consideration.

7.3.2

Permissible cable lengths

To operate the 9350 braking units in a trouble−free manner, observe the
following installation instructions:

Cable

9351 brake module

9352 brake chopper

[m]

[m]

Controller − 935X (low−inductance
cables, i. e. conduct in a bunched
manner)

2

2

935X − external brake resistor

(internal brake resistor)

8

Synchronisation cable between 935X
(only for parallel operation)

2

2