5.7.3 WibNet

– Monitor Comms

Figure 96 - WibNet Monitor Comms

The above screen shot shows the Received and Transmitted WibNet data frames.

The Table below shows an excerpt from the above screen shot.

Data frames are displayed similar to the WibMesh Monitor Radio Comms except the
data is a different format.

Below that is another table explaining each of the field within the data frame.

Time

Source IP

Dest IP

Len

Type

Seq

Ack

Dest

Cnt

Val

03:02:45.073629

192.168.2.146.51891

192.168.2.143.4370

7

WRITE

9

1

1

11111110

03:02:45.075693

192.168.2.143.56678

192.168.2.146.4370

1

ACK

9

Time

Message Time Stamp

– Time from when module was last started

Header

Displays if message is a receive (In) or a transmit (Out) as well as the
type and size of the Ethernet frame

Source IP

Originating or Source IP Address

Dest IP

Destination IP Address

Len

Total length of WEIDMULLER data

Type

Type of Message, i.e. Write, Read, Gather /Scatter, Etc.

Seq

Sequence number of the message

Ack

Indicates if the Weidmuller data frame is configured to acknowledge or
not acknowledged. This is configured in each mapping.

Dest

I/O address at the destination

– where the data will be written to or read

from.

Cnt

Total I/O count from the “dest” address above

Val

Data values

– the number of value will depend on I/O count.