Appendix c, Expansion i/o registers, Appendix c: expansion i/o registers – Weidmuller WI-I/O-9-U2: Wireless Mesh I/O & Gateway User Manual V1.2.2 User Manual
Page 115

114
Appendix C: Expansion I/O Registers
Adding Expansion I/O modules to the WI-I/O 9-U2 will automatically add
the I/O from the WI-I/O-EX-1-S modules to the internal WI-I/O 9-U2 I/O
store.
To calculate the register location in the I/O Store find the address of the
I/O point in the tables below and add the offset.
The Offset is the Modbus address multiplied by 20.
E.g1. Digital input #1 on an WI-I/O-EX-1-S-11 with address 5 would be: (5x20)
+10001 = 10101
E.g2. Digital output #2 on an WI-I/O-EX-1-S-11 with address 6 would be: (6x20) +2
= 122
E.g3. Analog input #3 on an WI-I/O-EX-1-S-12 with address 3 would be: (3x20)
+30003 = 30063.
E.g4. Analog Output #8 on an WI-I/O-EX-1-S-13 with address # 7 would be: (7x20)
+ 40007 = 40147
I/O store for a WI-I/O-EX-1-S-11 Expansion I/O module
0001 + Offset
0016 + Offset
DIO Outputs 1 - 16
10001 + Offset
10016 + Offset
DIO Inputs 1 - 16
10019 + Offset
Modbus Comms Fail indication for this WI-I/O-EX-1-S module
10020 + Offset
Modbus Comms Fail indication (Inverse) for this WI-I/O-EX-1-S
module
30001 + Offset
30004 + Offset
WI-I/O-EX-1-S-11 pulsed input rate 1
– 4
30005 + Offset
30012 + Offset
WI-I/O-EX-1-S-11 Pulsed input count
30017 + Offset
Modbus Error Counter for this WI-I/O-EX-1-S module
30018 + Offset
Modbus Last Error Code for this WI-I/O-EX-1-S module. (Section
5.1.3
30019 + Offset
Modbus Lost Link Counter for this WI-I/O-EX-1-S module
30020 + Offset
Module type (0x0101) = 257. / Error Status
40009 + Offset
40016 + Offset
Pulsed Output target 1
– 8 (1 register per pulsed output)