Appendix C: Expansion I/O Registers

Adding Expansion I/O modules to the WI-I/O 9-U2 will automatically add
the I/O from the WI-I/O-EX-1-S modules to the internal WI-I/O 9-U2 I/O
store.

To calculate the register location in the I/O Store find the address of the
I/O point in the tables below and add the offset.

The Offset is the Modbus address multiplied by 20.

E.g1. Digital input #1 on an WI-I/O-EX-1-S-11 with address 5 would be: (5x20)
+10001 = 10101

E.g2. Digital output #2 on an WI-I/O-EX-1-S-11 with address 6 would be: (6x20) +2
= 122

E.g3. Analog input #3 on an WI-I/O-EX-1-S-12 with address 3 would be: (3x20)
+30003 = 30063.

E.g4. Analog Output #8 on an WI-I/O-EX-1-S-13 with address # 7 would be: (7x20)
+ 40007 = 40147

I/O store for a WI-I/O-EX-1-S-11 Expansion I/O module

0001 + Offset

0016 + Offset

DIO Outputs 1 - 16

10001 + Offset

10016 + Offset

DIO Inputs 1 - 16

10019 + Offset

Modbus Comms Fail indication for this WI-I/O-EX-1-S module

10020 + Offset

Modbus Comms Fail indication (Inverse) for this WI-I/O-EX-1-S
module

30001 + Offset

30004 + Offset

WI-I/O-EX-1-S-11 pulsed input rate 1

– 4

30005 + Offset

30012 + Offset

WI-I/O-EX-1-S-11 Pulsed input count

30017 + Offset

Modbus Error Counter for this WI-I/O-EX-1-S module

30018 + Offset

Modbus Last Error Code for this WI-I/O-EX-1-S module. (Section
5.1.3

30019 + Offset

Modbus Lost Link Counter for this WI-I/O-EX-1-S module

30020 + Offset

Module type (0x0101) = 257. / Error Status

40009 + Offset

40016 + Offset

Pulsed Output target 1

– 8 (1 register per pulsed output)