62

parameters.

Digital Inputs

By selecting an Input in this display and then pressing
the Edit button it will allow you to make changes to
the input.

Name

The inputs can be named to help with

configuration or use the default, up to 30 characters
including spaces.

Debounce Time (sec)

Debounce is the time which

an input must stay stable before the module decides that a change of state has
occurred. If a digital input changes (on - off) and changes again (off - on) in less than
the debounce time, then the module will ignore both changes. Default debounce time is
0.5 seconds.

Digital Outputs

Name

The Outputs can be named to help with

configuration or use the default, up to 30 characters
including spaces.

Failsafe Time (sec)

The Fail Safe Time is the time

the output needs to count down before activating the
failsafe state. Receiving an update or a COS message
will reset the Fail Safe Timer back to its starting value.
If the Fail Safe Timer gets down to zero then the output will be set to the Fail Safe state
(ON or OFF)

It is recommend this Fail Safe Time be configured for a little more than twice the update
time of the input that is mapped to it, that way the output will reset if it fails to receive
two update messages.

Fail Safe State

The state that the output will go to after the ‘Failsafe Time’ has

elapsed.

If the Failsafe state is enabled (ON) this will indicate with the LED flashing briefly OFF
and the digital output will turn on.

If the Failsafe state is disabled (OFF) this will indicate with the LED flashing briefly ON
and the digital output will turn off.

Pulsed Outputs

Name

The inputs can be named to help with

configuration or use the default, up to 30
characters including spaces.

Update Time (sec)

Time that the output will

be updated with the latest received value. The
time is related to the update time of the pulsed
input that is mapped to it. E.g. If the pulsed input
update time is configured for 10 seconds the number of pulses will be counted and sent

Figure 42 - Digital Inputs

Figure 43 - Digital Output

Figure 44 - Pulsed Outputs