Weidmuller WI-I/O-9-U2: Wireless Mesh I/O & Gateway User Manual V1.2.2 User Manual

Page 109

Advertising
background image

108

RS232 Port

EIA-562 (RJ45 Connector)

RS485 Port

2-Pin Terminal Block

– Non-Isolated

(6)

Data Rate (Bps)

1200, 2400, 4800, 9600, 14400, 19200, 38400, 57600, 76800,
115200, 230400bps

Serial Settings

7 / 8 Data Bits; Stop/Start/Parity (Configurable)

Protocols and Configuration

System Address

ESSID; 1

– 31 Character Text String

Protocols Supported

TCP/IP, UDP, HTTP, FTP, TFTP, TELNET, MODBUS RTU
Master/Slave, MODBUS-TCP Client/Server

User Configuration

All User Configurable Parameters via HTTPS

Configurable
Parameters

Unit details, I/O mappings and parameters, radio settings, for
more refer to user manual.
Modbus TCP/ RTU Gateway
Embedded Modbus Master/Slave for I/O transfer

Security

Data Encryption

– 256bit AES. Secure HTTP Protocol

LED Indication/Diagnostics

LED Indication

Power/OK; TX/RX; RS232; RS485; Digital I/O; Analog I/O
status

Reported Diagnostics

RSSI Measurements (dBm), Connectivity Information/Statistics,
System Log file

Network Management

Optional Network Management System

Compliance

EMC

FCC Part 15; EN 301 489; AS 3548

RF (Radio)

FCC Part 15.247; AS 4268.2 ; RFS29 NZ

Hazardous Area

CSA Class I, Division 2; ATEX; IECEx Na IIC

Safety

IEC 60950 (RoHS Compliant)

UL

UL Listed

General

Size

180 x 150 x 35 mm (5.91” x 7.09” x 1.38”)

Housing

IP20 Rated High Density Thermoplastic

Mounting

DIN Rail

Terminal Blocks

Removable; Max conductor 12AWG (2.5 mm2)

Temperature Rating

-40 to +60°C; -40 to +140°F

Humidity Rating

0

– 99% RH Non-condensing

Weight

0.5kg (1.1lb).

Power Supply

Nominal Supply

10.8 to 30Vdc; Under/ Over Voltage Protection

Average Current

220mA @ 12V (Idle), 110mA @ 24V (Idle)

Advertising