4.3.8 Standard WI-I/O 9-U2 I/O (Basic I/O)

The following table shows the basic onboard I/O available in a standard WI-I/O 9-U2
module with no expansion I/O connected. For a more detailed I/O map (showing the full
register range), see Appendix B:

“I/O Store Registers” at the end of the manual.

Address

Input / Output Description

0001 - 0008

Local DIO1

– DIO8 (as Outputs)

10001 - 10008 Local DIO1

– DIO8 (as Inputs)

10009 - 10020

Setpoint status from Analog inputs 1 through 12. (AI1, 2, 3, 4
Current Mode), (Internal Supplies), (AI1, 2, 3, 4 Voltage Mode)

30001 - 30004

Local AI1

– AI4 (Current Mode)

(AI1& AI2 - 4-20mA diff, AI3 & AI4 - 4-20mA Sink)

30005

30006

30007

30008

Local Supply voltage (0-40V default scaling)

Local 24V loop voltage (0-40V default scaling)

Local Battery voltage (0-40V default scaling)

WI-I/O-EX-1-S Expansion I/O Supply Voltage (0-40V default
scaling)

30009 - 30012 Local AI1

– AI4 (Voltage Mode) (AI1& AI2 - 0-20V, AI3 & AI4 - 0-5V)

30013 - 30016 Local Pulse input rates PI1

– PI4

36001 - 36008

Local Pulsed input counts

– (PI1 Most significant word is 36001 and

Least significant word is 36002)

38001 - 38032 Local Analog inputs as Floating point values (mA, Volts or Hz)

40001 - 40002 Local AO1

– AO2

48001 - 48002 Local AO1

– AO2 as floating point values (mA)

4.3.9 I/O Configuration

I/O configuration is done using the
Configuration software and each I/O has
different characteristics that can be tailored to
certain applications.

Selecting IO from within the Project Tree in
the Configuration utility will display
configuration options for the I/O, the
configuration display (explained below) will
provide an overview for all of the configurable

Figure 41 - I/O configuration