117

65286

FF06

Slave Device
Busy

Specialized, use in conjunction with programming
commands.

The server (or slave) is engaged in processing a long

duration program command. The client (or master)
should retransmit the message later when the server (or
slave) is free.

65288

FF08

Memory
Parity Error

Specialized, use in conjunction with function codes 20
and 21 and reference type 6, to indicate that the
extended file area failed to pass a consistency check.

65290 FF0A

Gateway
Path
Unavailable

Specialized, use in conjunction with gateways. Indicates
that the gateway was unable to allocate an internal
communication path from the input port to the output
port for processing the request. Usually means that the
gateway is misconfigured or overloaded.

65291 FF0B

Gateway
Device Failed
to Respond

Specialized, use in conjunction with gateways. Indicates
that no response was obtained from the target device.
Usually means that the device is not present on the
network

65024 FE00

Invalid
Response
from Slave

Command type or Slave address did not match request
(probably another unit)

64512 FC00 Server Offline

Couldn’t connect to Modbus TCP server

63488

F800

Invalid Local
Memory
Address

Local address invalid in command - Memory location
does not exist or is not initialised.

65535 FFFF

No Response
to the Poll

No response to poll message