AutoMax DCSNet/RE RIO Module Page

13

Publication number 56AMXN-UM002A-EN-P November 2002

The network coaxial cable must be terminated with 75 ohm terminating
loads attached to the taps at the physical ends of the network. There
should be two and only two terminators on the network.

For DCS, the network cable can be RG-59/U or RG-11/U. For remote
I/O, the cable must be RG-59/U.

Software Installation

The 56AMXN is supplied with a CD that includes the configuration and
monitoring programs for the 56AMXN.

RSLinx should be installed before you install the 56AMXN software.
The 56AMXN software requires RSLinx OEM or Professional; it does
not work with RSLinx Lite.

You must delete any previous version of the 56AMXN software before
you can install a new version. Use the Windows Control Panel Add and
Remove Programs to remove the old version.

Insert the 56AMXN CD with the module software and run the program
setup.exe on the CD.

Messages about DTL32.DLL when you install or run the programs
indicate problems with the RSLinx installation. Confirm that you are
have RSLinx OEM or RSLinx Professional (not RSLinx Lite) installed.