Instance level services, Get attribute single, service code 0eh – Rockwell Automation 56AMXN/B ControlLogix AutoMax Comm Module User Manual

Page 41

Advertising
background image

AutoMax DCSNet/RE RIO Module Page

41

Publication number 56AMXN-UM002A-EN-P November 2002

Service

(hex)

Name Function

04h

Set Attribute List

Set the data for up to 7 drops

0eh

Get Attribute Single

Get the data for a single drop

10h

Set Attribute Single

Set the data for a single drop

32h

DCS Register Raw Write

Write a block of data to the
DCS registers on the 56AMXN

33h

DCS Register Raw Read

Read a block of data from the
DCS registers on the 56AMXN

36h

Write Multiple Drops

Set the data for up to 7 drops

37h

Read Multiple Drops

Get the data for up to 7 drops

Table 9 DCS Data Object Instance Services

Instance Level Services

You use instance level services to read and write register data on DCS
drops. Which data you can write depends on whether the module is a
DCS master or slave.

Get Attribute Single, Service Code 0Eh

Note: for best performance, we recommend you use the Read Multiple
Drops command (page 48), especially if you are reading the data for
more than one drop.

To read the instance level attributes for a single attribute (drop), enter the
following parameters in the MSG instruction tags:

Message
Type

CIP generic

Service Type

Get Attribute Single

Service Code 0Eh (grayed out)

Class (hex)

C4h

Instance

1 for registers 0-31

2 for registers 32-63

Attribute (hex) Corresponds to the drop number, range 0-55. Note that

you enter the attribute in hex in RSLogix 5000

Source
Element

(grayed out)

Source (grayed

out)

Advertising
This manual is related to the following products: