DCS Raw Read, Service Code 33h

The DCS raw read command can be used to read a block of data from the
DCS data area on the module. You tell it the starting offset and the data
length and it reads the data.

Enter the following parameters in the MSG instruction tags:

Message
Type

CIP generic

Service Type

Custom

Service Code 33h

Class (hex)

C4h

Instance 1

Attribute (hex) Leave blank

Source
Element

Enter source tag name

Source
Length (bytes)

4 (offset + length)

Destination

Enter destination tag name, must be large enough to
hold the data

Table 17 DCS Data Object DCS Raw Read Parameters

In the source tag

First word

offset in words = drop * 64 + register, range is 0 to 55 *
64 + 63 = 3583

Second word

Length in words, 1 to 230

Read Multiple Drops, Service Code 37h

This command is similar in purpose to Get Attribute List, except that the
layout of the data is more intuitive and makes it easier to locate the data
for a specific drop and register. The format for Get Attribute List is set
by the ControlNet specification and can’t be changed.

Read Multiple Drops does not support drop 0.

Enter the following parameters in the MSG instruction tags: