If you create an array organized as Data[number of drops][32] to hold the
returned data, it makes it very easy to locate the data for each drop and
register.

Write Multiple Drops, Service Code 36h

This command is similar in purpose to Set Attribute List, except that the
layout of the data is more intuitive and makes it easier to locate the data
for a specific drop and register. The format for Set Attribute List is set
by the ControlNet specification and can’t be changed.

If you write data that is also mapped as scheduled data, the data you
write will be overwritten when the next scheduled data update occurs.

Enter the following parameters in the MSG instruction tags:

Message
Type

CIP generic

Service Type

Custom

Service Code 36h

Class (hex)

C4h

Instance

1 for registers 0-31 (slave)

2 for registers 32-63 (master)

Attribute (hex) leave blank

Source
Element

enter source tag name

Source
Length (bytes)

2 + [number of drops] * 66, see table below

Destination

enter destination tag name, not used but must be
entered

Table 19 Write Multiple Drops Parameters

Message format in the source tag:

Data for the first drop in the list, 32 words

Data for the second drop in the list, 32 words