Rockwell Automation 56AMXN/B ControlLogix AutoMax Comm Module User Manual

Page 22

Advertising
background image

Page

22

AutoMax DCSNet /RE RIO Module

Publication number 56AMXN-UM002A-EN-P November 2002

Register 16 contains CRC errors. This counter increments when the
module receives a packet with a bad CRC.

Register 17 contains overrun errors. This counter increments when the
module receives a packet that is longer than 272 bytes.

Register 18 contains abort errors. This counter increments when the
module starts to receive a packet but the packet is never completed.

Register 19 contains a running count of messages transmitted.

Offset Description

4

Drop status, drops 0 – 15

5

Drop status, drops 16 - 31

6

Drop status, drops 32 – 47

7

Drop status, drops 48 – 55

12

56AMXN drop number

14 Messages

received

15 Receive

timeouts

16 CRC

errors

17 Overrun

errors

18 Abort

errors

19 Messages

transmitted

20

56AMXN drop depth

Table 5 Diagnostic Registers

For example, if you set Local:0:C.InputDropMap[4].Block[3] to 0, then
Local:0:I4.Block[3].Data contains the diagnostic counters, in
Local:0:I4.Block[3].Data[0] to Local:0:I4.Block[3].Data[31]

Note: You cannot map the diagnostic counters more than once.