AutoMax DCSNet /RE RIO Module

Publication number 56AMXN-UM002A-EN-P November 2002

Figure 6 Module Properties 1

7. Set the module RPI. This is how often the module’s scheduled data

is updated in the processor. The value can range from 3.0 to 750 ms.
The default is 3 ms. The listen only RPI should match the RPI for
the owning ControlLogix.

8. Click Finish >> to complete the module configuration.

9. Save the program and download it to the ControlLogix processor.

Remote I/O Master

To configure the module in RSLogix 5000, you must be offline.

1. If you are creating a new project, select File/New to create a new

project, give the processor a name, and enter the slot it occupies in
the ControlLogix rack.

2. Right click on I/O configuration and select New Module…

3. Select a module of Type 1756-MODULE, Description Generic 1756

Module from the list and Click OK. RSLogix 5000 displays the
Module Properties – Local dialog box.