AutoMax DCSNet /RE RIO Module

Publication number 56AMXN-UM002A-EN-P November 2002

Length (bytes)

Destination

Enter the destination tag name, must be large enough
to hold the data, make it an integer array of size at
least 32 integers

Table 10 DCS Data Object Instance Level Get Attribute Single Parameters

This command can be used to read the DCS data for any drop, including
drop 0. You enter the drop number as the attribute, and use the instance
to select whether you want to read registers 0-31 or 32-63.

The command returns the data in 32 consecutive integers in the
destination tag.

Set Attribute Single, Service Code 10h

Note: for best performance, we recommend you use the Write Multiple
Drops command (page 50), especially if you are writing the data for
more than one drop.

To set the instance level attributes for a single attribute (drop), enter the
following parameters in the MSG instruction tags:

Message
Type

CIP generic

Service Type

Set Attribute Single

Service Code 10h (grayed out)

Class (hex)

C4h

Instance

1 for registers 0-31

2 for registers 32-63

Attribute (hex) Corresponds to the drop number, range 0-55. Note that

you enter the attribute in hex in RSLogix 5000

Source
Element

Enter source tag, make it an integer array of size at
least 32 integers

Source
Length (bytes)

64 (bytes), but see below for attribute 0

Destination (grayed

out)

Table 11 DCS Data Object Instance Level Set Attribute Single Parameters

This command can be used to write the DCS data for any drop, including
drop 0. You enter the drop number as the attribute, and use the instance
to select whether you want to write to registers 0-31 or 32-63. Normally