Dcs slave – Rockwell Automation 56AMXN/B ControlLogix AutoMax Comm Module User Manual

Page 19

Advertising
background image

AutoMax DCSNet/RE RIO Module Page

19

Publication number 56AMXN-UM002A-EN-P November 2002

InputDropMap Value

Description

1 to 55

Drop data from drops, registers 0 to 31

56 Unused

Any other

Invalid

OutputDropMap Value Description

1 to 55

Drop data to remote drops, registers 32 to 63

56 Unused

Any other

Invalid

DCS Slave

InputDropMap Value

Description

0

56AMXN Status/diagnostic registers

1 to 55

Drop data, registers 32 to 63, from master

-1 to –55

Drop data, slave to master, registers 0 to 31,
from monitored drops

56 Unused

Any other

Invalid

OutputDropMap Value Description

1 to 55

Drop data, registers 0 to 31, from 56AMXN to
master

56 Unused

Any other

Invalid

Duplicate entries in the InputDropMap or OutputDropMap areas are
invalid. The only exception is that there can be multiple blocks marked
as unused (56).

If the configuration tag contains invalid data, the connections to the
56AMXN do not open. The ControlLogix periodically retries the
connections so if you correct the invalid configuration data, the
connections will eventually open.

However, if you change the contents of a valid configuration tag in the
ControlLogix, you must break and remake the connections to the
56AMXN to cause the 56AMXN to use the modified configuration data.