Operating behavior

As the trip mode Max or Min are possible, as the operating mode Active or Passive are possible.
Areas of application:
• Trip mode Max, operating mode Active: alarm if the signal is above the trip value, e. g. horn on;

protection against overfilling, e. g. open drain in capacity tank

• Trip mode Max, operating mode Passive: protection against overfilling, e. g. conveyor belt/pump

off; for a large hysteresis Min-Max operation, e. g. conveyor belt/pump on/off

• Trip mode Min, operating mode Active: alarm if the signal is below the trip value, e. g. horn on;

protection against shortfalls in security reserves, e. g. conveyor belt/pump on

• Trip mode Min, operating mode Passive: Protection against shortfalls in security reserves, e. g.

pumping out off; for a large hysteresis Min-Max operation

The exact operating behavior of the Strain Gauge Converter is illustrated in the following figure:

Delay

——

0 sec. to 250 sec.

Alarm freeze

——

On

Off

Hold on error

——

On

Off