The commands must be encoded as follows:

The

Strain Gauge Converter returns the following responses:

Explanations:

Address: The address must be calculated as follows: 128 + setting under Service

RS 485 (see

section 7.8). Values from 128 + 0 to 128 + 31, i. e. from 10000000

Bin

to 10011111

Bin

, are possible.

Checksum: The checksum is calculated as follows: 100

Hex

- (1

st

byte + ... + penultimate byte of the

code), e. g. for Check_1 for address 17: 100

Hex

- (91

Hex

+ 1) = 6E

Hex

= 01101110

Bin

The figure 9 in the response to Check_1 refers to the device type

Strain Gauge Converter.

Value: in the signed long data format (4 bytes or 2 bytes)

Command

1

st

byte

2

nd

byte

3

rd

byte

4

th

byte

5

th

byte

6

th

byte

Null

0

0

0

0

0

0

Check_1

Address

1

Checksum

Get_value_ch1

Address

B

Hex

Checksum

Get_value_ch2

Address

C

Hex

Checksum

Get_value_ch3

Address

10

Hex

Checksum

Get_current

Address

D

Hex

Checksum

Command

1

st

byte

2

nd

byte

3

rd

byte

4

th

byte

5

th

byte

6

th

byte

Check_1

Address

9

Checksum

Get_value_ch1

Address

Value

Checksum

Get_value_ch2

Address

Value

Checksum

Get_value_ch3

Address

Value

Checksum

Get_current

Address

Value

Checksum

Bul. 937

C Strain Gauge Converter Installation Instructions