C Strain Gauge Converter Installation Instructions

Characteristic

The settings have the following meaning (for Inverted

normal)

Selected setting 20.20 -/+mA

This setting converts the measured value 0 into -20 mA (i.

e. into 20 mA in the case of changed polarity

at the terminals 7 and 8), the span is converted into +20 mA
(terminal 7 -, terminal 8 +), interim values are calculated proportionally.

For values below the measured value 0, the output current decreases linearly to a minimum of
-20.5 mA (-1.25 % of the measurement range). Further underflows cannot be evaluated (output
-20.5 mA). If the span is exceeded, the output current increases linearly to a maximum of +20.5 mA
(101.25 % of the measurement range). Further increases cannot be evaluated (output +20.5 mA).

Selected setting 4 - 20 NE 43

+ 20.5
+ 20.0

0

- 1.25 %

0

100 % = span

101.25 %

mA

Measured

- 20.0
- 20.5

value

20.5
20.0

0

0

100 % = span

≈ 103 %

- 1.25 %

mA

Measured

4.0
3.8

value