Delay – Rockwell Automation 937CU-AISTR-DC1 Strain Gauge Converter Installation Instructions User Manual

Page 30

Advertising
background image

Bul. 937

C Strain Gauge Converter Installation Instructions

As the representation of the operating

behavior in section 7.6.2 shows, the following must apply:

− for the trip mode Max: trip point - hysteresis ≥ 0

− for the trip mode Min: trip point + hysteresis ≤ upper limit of the trip point
The limits are automatically determined by the

Strain Gauge Converter being.

The hysteresis should be > 1 % of the trip point in order to prevent rapid switching of the relay.

Delay

If you set a time > 0 sec, you prevent short-time violations of the trip value from triggering an alarm.

The relay only switches if the trip point is exceeded/fallen short of for a period that is longer than
the delay time.

The relay only switches back if the trip point -/+ hysteresis is fallen short of/exceeded for a period
that is longer than the delay time.

If the trip point is exceeded/fallen short of for a short time, this does not have any effects.

The following figure shows the operating

behavior for the trip mode Max, operating mode Active.

Time

Trip mode Max, operating mode Active, with delay
energised
de-energised

Delay

Delay

Max - hysteresis

Max

Measured
value

28

Advertising