Selected setting 0 - 20 mA (b)

This setting converts the measured value 0 into 0, the span (see section 7.7.1) is converted into
20 mA, interim values are calculated proportionally.

Values below the measured value 0 cannot be evaluated (output 0 mA). If the span is exceeded, the
output current increases linearly to a maximum of 20.5 mA (102.5 % of the measurement range).
Further increases cannot be evaluated (output 20.5 mA).

Fault current

The following table shows what the current output is during a fault, depending on the selected setting:

Setting

Characteristic
20.20 -/+mA

Characteristic
4 - 20 NE 43

Characteristic
12.20 -/+mA

Characteristic
0 - 20 mA (b)

Min
(downscale)

-21.5 mA

2.0 mA

-21.5 mA

0 mA
(cannot be
distinguished from
measurement

≤ 0)

Max
(upscale)

+21.5 mA

21.5 mA

+21.5 mA

21.5 mA

Hold

last value before the fault

Up/down

in the case of Err Cell: downscale; in all other cases: upscale

20.5
20.0

0

0

100 % = span

102.5 %

mA

Measured
value

Bul. 937

C Strain Gauge Converter Installation Instructions

34