Fault current – Rockwell Automation 937CU-AISTR-DC1 Strain Gauge Converter Installation Instructions User Manual
Page 36

Selected setting 0 - 20 mA (b)
This setting converts the measured value 0 into 0, the span (see section 7.7.1) is converted into
20 mA, interim values are calculated proportionally.
Values below the measured value 0 cannot be evaluated (output 0 mA). If the span is exceeded, the
output current increases linearly to a maximum of 20.5 mA (102.5 % of the measurement range).
Further increases cannot be evaluated (output 20.5 mA).
Fault current
The following table shows what the current output is during a fault, depending on the selected setting:
Setting
Characteristic
20.20 -/+mA
Characteristic
4 - 20 NE 43
Characteristic
12.20 -/+mA
Characteristic
0 - 20 mA (b)
Min
(downscale)
-21.5 mA
2.0 mA
-21.5 mA
0 mA
(cannot be
distinguished from
measurement
≤ 0)
Max
(upscale)
+21.5 mA
21.5 mA
+21.5 mA
21.5 mA
Hold
last value before the fault
Up/down
in the case of Err Cell: downscale; in all other cases: upscale
20.5
20.0
0
0
100 % = span
102.5 %
mA
Measured
value
Bul. 937
C Strain Gauge Converter Installation Instructions
34