Strain Gauge Converter can request the following information via the RS 485 interface e. g.

from a PC or a PLC (with 3 decimal places each):

Net measured value (in the set unit

)

Gross measured value (in the set unit)

mV measured value (

in the set unit)

Output value current output (in mA)

The following commands are available for the requests:

Null: delete the receive buffer of the requesting device

Check_1: checks whether

Strain Gauge Converter (with the respective address) is connected

Get_value_ch1: requests the net measured value

Get_value_ch2: requests the gross measured value

Get_value_ch3: requests the mV measured value

Get_current: requests the output value current output

Requests via the RS 485 interface are not suitable for time-critical or safety-critical
applications.

At the beginning of each RS

485 communication, send the request Check_1.

The RS

485 interface is deactivated if a connector is plugged into the programming

jack (RS

232 interface).

When the connector is removed, the request Check_1 is required to switch to RS

485

communication.