Trip point and Hysteresis

When entering the values for the trip point and hysteresis, please observe the following:
• By means of the Gross/Net parameter, you determine whether the value for the trip point is a gross

value or a net value (gross value minus current tare).

• The trip point and hysteresis must be entered in the selected unit.

− The minimum value for the trip point is 0, the minimum value for the hysteresis is 0.1.

− If you have selected Gross, the maximum ce ll load is the maximum value for

the trip point and hysteresis.

− If you have selected Net, the value of the maximum cell load minus the current tare

is the maximum value for the trip point and hysteresis.

Min

Min + hysteresis

Max - hysteresis

Max

Measured value

Time

Trip mode Min, operating mode Passive:

energized

de-energized

Trip mode Min, operating mode Active:

energized

de-energized

Trip mode Min, operating mode Passive:

Trip mode Min, operating mode Active:

energized

de-energized

energized

de-energized