Rockwell Automation 1397 DC Drive Firmware 2.xx User Manual
Page 148

5–38
Programming Parameters
Publication 1397-5.0 — June, 2001
FEATURE SELECT
[Min Speed Bypass] — P.099
Disables the [Min Process Spd] limit when
“ON”. When “Off” the [Min Process Spd] is
the lower limit.
Display/Drive Units:
Numeric/Text
Parameter Type:
Selectable
Group:
Feature Select
Factory Default:
0
Minimum Value:
0 = Off
Maximum Value:
1 = On
ATTENTION: This drive can operate at and maintain zero speed when
this parameter is set to on. The user is responsible for assuring safe
conditions for operating personnel by providing suitable guards, audible
or visual alarms, or other devices to indicate that the drive is operating at
or near zero speed. Failure to observe this precaution could result in
severe bodily injury or loss of life.
!
[Ref Ramp Bypass] — P.100
Bypasses the Speed Loop Ramp block. The
bypass is automatically overridden during a
stop command.
Note: If bypassed, rapid speed change can
result.
Display/Drive Units:
Numeric/Text
Parameter Type:
Tunable
Group:
Feature Select
Factory Default:
0
Minimum Value:
0 = Off
Maximum Value:
1 = On
[Current Compound] — P.101
Sets the level of current compounding to be
used during any mode of drive operation.
Display/Drive Units:
%FLA
Parameter Type:
Tunable
Group:
Feature Select
Factory Default:
0%
Minimum Value:
–50%
Maximum Value:
50%