Rockwell Automation 1397 DC Drive Firmware 2.xx User Manual
Page 67

3–9
Programming Terminal
Publication 1397-5.0 — June, 2001
EEProm Mode
or
or
Reset Defaults
or
or
Drive –> HIM
The EEProm mode is used to restore all settings
to factory default values or upload/download
parameters between the HIM and Drive.
1. To restore factory defaults:
A. From the Status Display, press Enter (or
any key). “Choose Mode” will be
displayed.
B. Press the Increment (or Decrement) key
until “EEProm” is displayed. If EEProm
is not in the menu, programming is
password protected. Refer to Password
Mode later in this section.
C. Press Enter.
D. Press the Increment (or Decrement) key
until “Reset Defaults” is displayed.
E. Press Enter to restore all parameters to
their original factory settings.
F. Press the Stop key to reset the fault, if
one occurs.
2. To upload a parameter profile from the
Drive to the HIM:
A. From the EEProm menu (see steps A-C
above), press the Increment/Decrement
keys until “Drive –> HIM” is displayed.
B. Press Enter. A profile name (up to 14
characters) will be displayed on line 2 of
the HIM. This name can be changed or a
new name entered. Use the SEL key to
move the cursor left. The Increment/
Decrement keys will change the
character.
Choose Mode
Display
Choose Mode
EEProm
EEProm
Reset Defaults
EEProm
Drive –> HIM
Drive –> HIM
1 A