Rockwell Automation 1397 DC Drive Firmware 2.xx User Manual
Page 157

5–47
Programming Parameters
Publication 1397-5.0 — June, 2001
INPUT CONFIG
[Anlg In 1 Gain] — P.127
Used to scale the analog input 1 signal after it
has been conditioned by the drive hardware.
Typically, it will be 1.000.
Display/Drive Units:
Numeric
Parameter Type:
Tunable
Group:
Input Cong
Factory Default:
1.000
Minimum Value:
0.750
Maximum Value:
2.250
[Anlg In 1 Type] — P.128
Selects the analog input 1 signal type.
Note: Jumpers J10 and J12 must be set for
the same type of signal selected by this
parameter.
Display/Drive Units:
Numeric
Parameter Range:
0 = 0-10V
1 =
±10V
2 = 4 -20mA
3 = 10-50mA
Parameter Type:
Configurable
Group:
Input Config
Factory Default:
0
Minimum Value:
0
Maximum Value:
3
[Anlg In 1 Zero] — P.129
Used to remove any hardware introduced
offset from the analog auto reference signal.
Typically, it will be 0.
Display/Drive Units:
Numeric
Parameter Type:
Tunable
Group:
Input Config
Factory Default:
0
Minimum Value:
–200
Maximum Value:
200
[Anlg In 2 Gain] — P.130
Scales the manual mode analog reference
signal after it has been conditioned by the
drive hardware. Typically, it will be 1.000.
Display/Drive Units:
Numeric
Parameter Type:
Tunable
Group:
Input Config
Factory Default:
1.000
Minimum Value:
0.750
Maximum Value:
2.250