FEATURE SELECT
[Trim Reference] — P.120
Drive register to manually set the trim
reference value used by the drive.
Display/Drive Units:
%
Parameter Range:
±100.0%
Parameter Type:
Tunable
Group:
Feature Select
Factory Default:
0
Minimum Value:
–100%
Maximum Value:
+100%
[OCL Enable Src] — P.121
Sets the source of the OCL enable signal.
“Register” means it comes from [OCL
Enable]. “Terminal Blk” means I/O Expansion
#64.
Display/Drive Units:
Numeric/Text
Parameter Range:
0 = Register
1 = Terminal Blk
Group:
Feature Select
Parameter Setting:
Tunable
Factory Default:
0
Minimum Value:
0
Maximum Value:
1
[Inertia Comp Reg] — P.122
Allows inertia compensation value to be
entered (via Datalink also) when Inertia Comp
Src P. 102 is set to “Register”. The value of
this parameter is not saved through a
power–cycle, it is reset to zero at power–up.
Display/Drive Units:
CNTS Counts
Parameter Range:
0 – 4095
Group:
Feature Select
Parameter Setting:
Tunable
Factory Default:
0
Minimum Value:
0
Maximum Value:
4095