Monitor 2 delay] — p.106, Monitor 2 source] — p.107 – Rockwell Automation 1397 DC Drive Firmware 2.xx User Manual
Page 151

5–41
Programming Parameters
Publication 1397-5.0 — June, 2001
FEATURE SELECT
[Monitor 2 Delay] — P.106
The delay time in seconds for the monitor 2
circuit. Refer to the Level Detectors block
diagram (A.12) for additional Information.
Display/Drive Units:
SECS
Parameter Type:
Tunable
Group:
Feature Select
Factory Default:
1.0 seconds
Minimum Value:
0 seconds
Maximum Value:
30.0 seconds
[Monitor 2 Source] — P.107
Selects the signal that drives monitor 2.
Display/Drive Units:
Numeric/Text
Parameter Range:
0 = Cur Lp Fdbk
1 = Spd Lp Fdbk
2 = Spd Ramp Out
3 = Spd Ramp In
4 = Spd Src Out
Parameter Type:
Configurable
Group:
Feature Select
Factory Default:
3 (Spd Ramp In)
Minimum Value:
0
Maximum Value:
4
Monitor 1
Output
(P13)
To I/O
Expansion
Outputs
Block Diagram
COMPARE
A
B
Monitor 1 Delay
(P103)
Start/Stop
Delay Time
TIMER
A > B
ABS
Monitor 1 Level
(P105)
Cur Lp Fdbk
Spd Lp Fdbk
Spd Ramp Out
Spd Ramp In
Spd Src In
Current Loop
Feedback Average
From Speed Loop Block Diagram
From Speed Reference
Ramp Block Diagram
From Speed Reference
Source Block Diagram