Determine cycle time of circuit diagrams, Determine cycle time of circuit diagrams -3 – Rockwell Automation 1760-xxxx Pico Controller User Manual User Manual
Page 171

Publication 1760-UM001D-EN-P - September 2005
Inside Pico 8-3
Determine Cycle Time of
Circuit Diagrams
The maximum cycle time of a circuit diagram must be known in order
to determine the maximum counter frequency or reaction time of
Pico.
Blank Cycle Time Calculation Tables can be found on page A-13 of
this manual.
1760-L12xxx Cycle Time
For 1760-L12xxx, the cycle time can be calculated as follows:
List of Times for Processing Function Relays
Function
Number
Time Duration
in µs
Total
Basic pulse
1
210
–
Refresh
1
3500
–
Contacts and bridged contact fields
–
20
–
Coils
–
20
–
Total rungs from the first one to the last
one, with empty ones in between
–
50
–
Connecting lines (only
)
–
20
–
Timing relays
–
–
–
Counters
–
–
–
Analog value function relays
–
–
–
Total
–
Number
1
2
3
4
5
6
7
8
Timing relays in µs
20
40
80
120
160
200
240
280
Counters in µs
20
50
90
130
170
210
260
310
Analog value processors in µs 80
100
120
140
160
180
220
260
,
,