Inputs, Ac models – Rockwell Automation 1760-xxxx Pico Controller User Manual User Manual
Page 195

Publication 1760-UM001D-EN-P - September 2005
Specifications A-5
Inputs
AC Models
Specification
1760-L12NWN
1760-L12NWN-ND
1760-L18NWN-EX
1760-L18NWN-EXND
Digital inputs 24V ac
Number
8
12
Status display
LCD (if provided)
LCD (if provided)
Electrical isolation
To power supply
No
No
Between Inputs
No
No
to the outputs
Yes
Yes
Rated voltage (sinusoidal)
off state
0 to 6V ac
0 to 6V ac
on state
14 to 26.4V ac
14 to 26.4V ac
Rated frequency
50/60 Hz
50/60 Hz
Input current
I1 to I6
(1760-L18NWN-xx also I9 to I10)
4 mA at 24V ac 50 Hz
4 mA at 24V ac 50 Hz
Input current
I7, I8
(1760-L18NWN-xx also I11 and
I12)
2 mA at 24V ac 50 Hz,
2 mA at 24V
2 mA at 24V ac 50 Hz,
2 mA at 24V
Delay time I1 to I8 and I9 to I12 (1760-L18-NWN-xx), From 0 to 1 and from 1 to 0
Debounce ON
80 ms (50 Hz), 66
.66
ms
(60 Hz)
80 ms (50 Hz), 66
.66
ms
(60 Hz)
Debounce OFF
20 ms (50 Hz), 16
.66
ms
(60 Hz)
20 ms (50 Hz), 16
.66
ms
(60 Hz)
Max. permissible cable length (per input)
I1 to I8 and
1760-L18NWN-xx I9 to I10
40m (131 ft)