Installation 2-17
To limit the current to 400 mA, connect a 1K
Ω resistor in series
upstream from the circuit as shown.
.
Connect 24 V dc Inputs
Use input terminals I1 to I8 (or I12 for 18-point Pico) to connect
push-buttons, switches, or 3- or 4-wire proximity switches. Given the
high off-state leakage current, do not use 2-wire proximity switches.
Example Using 1760-L12BWB-xx
Input
Specification
Input Signal Voltage Range
OFF signal: 0 to 5V dc
ON signal: 15V to 28.8V dc
Input Current
I1 to I6, I9 to I12, R1 to R12: 3.3 mA at 24V dc
I7 and I8: 2.2 mA at 24V dc
L1
1A
L2
L1
L2
I2
I3
I4
I5
I6
I7
I8
I1
100 to 240V ac
50/60Hz
Inputs x 100 to 240V ac
100 nF, 275V ac capacitor
1K
Ω
0.25W
resistor
24V dc
+24 V COM
I2
I3
I4
I5
I6
I7
I8
I1
Inputs x 24V dc (I7,I8 0 to 10V)
+24V
0V
1A