Cycle time – Rockwell Automation 1760-xxxx Pico Controller User Manual User Manual
Page 203

Publication 1760-UM001D-EN-P - September 2005
Specifications A-13
Cycle Time
1760-L12xxx
1760-L18xxx
Function
Number
Time Duration
in µs
Total
Basic pulse
1
210
Refresh
1
3500
Contacts and bridged contact fields
20
Coils
20
Circuit connections from the first one to the
last one, with empty ones in between
0
Connecting lines, only
20
Timing relays (see Table below)
Counters (see Table below)
Analog value function relays (see Table
below)
Total
Number
1
2
3
4
5
6
7
8
Timing relays in µs
20
40
80
120
160
200
240
280
Counters in µs
20
50
90
130
170
210
260
310
Analog value processors in µs
80
100
120
140
160
180
220
260
Function
Number
Time Duration (µs)
Total
Basic pulse
1
520
Refresh
5700
Contacts and bridged contact fields
40
Coils
20
Circuit connections from the first one to the
last one, with empty ones in between
70
Connecting lines, only
40
Timing relays (see Table below)
Counters (see Table below)
Analog value function relays (see Table
below)
Total
,
,
,
,