Additional Redundant Server Procedures 6-15
9. The unsynchronized SERVERB data should be similar to this:
10. Verify that the link is active and the databases are synchronized.
Setting up the Redundant ERDB
Complete the following procedure on SERVERB only:
1. Click Start
⇒
Programs
⇒
ProcessLogix Engineering Tools
⇒
DB
Admin.
2. In the Login dialog box, make these entries:
a. Key in >mngr< as the default User Name.
b. Key in >mngr1< as the default Password.
c. Key in SERVERB in the Server Name field.
3. Expand the trees to DBAdmin
⇒
ProcessLogix Node
⇒
Admin
Tasks.
4. Click Disable Replication.
a. Click OK to verify that the replication is disabled.
c. To set up the database on SERVERA, click Recover
Secondary Database.
d. Click Yes to recover Secondary Database.
e. At the Successfully Recovered Secondary Database window,
click OK.
5. Click Enable Replication.
a. Click Yes to proceed.
b. At the Successfully Enabled Database Replication, click OK.
6. Click Console
⇒
Exit.