At step 6, Step 10 o – Rockwell Automation 1757-SWKIT4000 ProcessLogix R400.0 Installation and Upgrade Guide User Manual
Page 173

Publication 1757-IN040B-EN-P - March 2002
Firmware Maintenance Procedures 7-15
3. Key in this command in the Open entry field:
>ntools -c -pg<
4. Click OK to launch the Network Tools application.
5. Click OK to acknowledge the warning about monitoring through
Control Builder.
6. Click Resume
to initiate network scan.
7. Click any CNB icon under the Desktop tree and wait for the
graphic of the chassis to appear in the Detail pane.
8. In the graphic of your chassis, click the CNB module with the
Network Address selected above.
9. Click Change ControlNet
to call up the Keeper Values
dialog box.
10. Confirm that the values listed for the parameters under the
Changes Tab on the dialog box match the following settings and
key in new values, as required.
TIP
If the RSLinx and PCIC driver services for system
communications in ControlNet mode are not
running, this command will start the services.
TIP
This may be the only module that appears in
the chassis graphic at this time.