Installing the 1785ĆKA5

Communication Adapter Module

Chapter 2

2-2

The 1785-KA5 module has three banks of DIP switches that let you select
various communication options. The switch assemblies and their
corresponding options are:

To set the

Use switch assembly

DH485 station address and baud rate

SWĆ1

DH+ station address and the auto route enable option

SWĆ2

DH485 and DH+ channel LINK_IDs

SWĆ3

Figure 2.1 shows the location of the switches on the 1785-KA5 module.

Figure 2.1

1785ĆKA5 communication adapter module switch assemblies (cat. no.

1785ĆKA5/B shown)

B7

B6

B5

B4

B3

B2

B1

B0
B3

B2

B1

B0
B3

B2

B1

B0

B4

B3

B2

B1

B0

SW-1

SW-2

SW-3

ON
OFF

ON (1)

switch assemblies

19191

DH485 BAUD RATE

DH485 STATION ADDRESS

DH+ STATION ADDRESS

DH485 CHANNEL DH+ IP LINK ID

DH+ CHANNEL LINK ID

RESERVED

AUTO ROUTE ENABLE

OFF (0)

LEGEND

Important: The 1785-KA5 uses the following convention:

on = binary 1
off = binary 0

Setting the Switches