Installing the 1785ĆKA5

Communication Adapter Module

Chapter 2

2-17

Use the following table to determine if the installation was
successful:

If the installation was Then

successful

-only the green LEDs flash on and off.

-the DIP switches are read. All DIP switches are read at this

time only. Changes you make after this time are ignored.

Important: Always power down the module before you change

DIP switch settings.

unsuccessful

-the red LED remains on and the green LEDs freeze at the

failed value

-the 1785ĆKA5 is removed from both the DH+ and DH485

networks. Originating devices can not send packets through

the module and do not receive responses.

Use the module’s LEDs and the following table to interpret an
installation failure:

DH+TX

DH+RX

DH485TX

Problem

off

off

on

bad ROM checksum

off

on

off

RAM address test failed

off

on

on

RAM pattern test failed

on

off

off

CTC timer tests failed

Important: If only the red FAULT LED lights up, there are two possible
causes:

a duplicate station address was detected on the DH+ or DH485
the KA5P is indicating that there is a problem with the external

power supply or cable