Installing the 1785ĆKA5

Communication Adapter Module

Chapter 2

2-13

Important: If the 1785-KA5 module is attached at either end of the
DH485 network trunk cable, install a wire jumper between pins 4 and 6 of
the 6-pin mating connector supplied with the module. This is the
termination resistor for the network.

5.

If you are connecting a 1785-KA5P/B panel-mount module, you need
to connect the external power supply:

Important: To meet the Low Voltage Directive regulations within the
European Union or EEA Regions, you must use a Class 2 Safety Extra-low
Voltage power supply.

a. Wire a power supply cable as shown below:

5V dc

supply @

3 Amps

4Ćpin PhoenixĆstyle connector

supplied with 1785ĆKA5P/B module

(CHASSIS GROUND) Green/Yellow

+5V dc Red

(connect to power

connector on the

1785ĆKA5P/B module)

(no connection)

0V dc (dc GND) Black

14 AWG standard colorĆcoded wire

4
3
2
1

The earth ground or chassis ground wire should be color-coded
green with a yellow stripe.

b. Wire the cable using the 4-pin connector you received with your

module and connect the cable to the EXT PWR connector on the
module.

Pin

Signal

1

no connection

2

+5V dc @ 2.0 amps (red)

3

0Vdc (dc GND) black

4

(Chassis Ground) green/yellow