Communicating through the 1785ĆKA5

Communication Adapter Module

Chapter 3

3-6

This section explains:

gateway mode addressing
how the 1785-KA5 operates as a gateway
“single-hop” mode packets

Gateway Mode Addressing

All DH+ and DH485 destination and source addresses are contained in the
lower address byte, leaving the upper byte free for “sub-addressing.” An
internet device sends a packet to a non-internet device on the DH485 link
by:

addressing the lower byte of the STATION address (D_STATION[0]) to

the 1785-KA5 adapter module for packet processing

addressing the upper byte of the STATION address (D_STATION[1]) to

the actual destination device. The upper byte of the STATION field is
defined as follows:

1785ĆKA5 Gateway

Communication

Advertising