most significant octal digit = 1

least significant octal digit = 7

Installing the 1785ĆKA5

Communication Adapter Module

Chapter 2

2-3

SWĆ1: DH485 Station Address and DH485 Baud Rate

Use switch assembly SW-1 to select the DH485 station address and baud
rate for the 1785-KA5 module. The following sections show you how.

Setting the DH485 Station Address
Set switches 1-5 of SW-1 to the DH485 station address for the 1785-KA5.
Valid addresses are 0-31 decimal or 0-37 octal. Set the switches as
follows:

Most significant octal digit (switches 1Ć2)

To set to

Set switch 1 to

Set switch 2 to

0

0

0

1

0

1

2

1

0

3

1

1

Least significant octal digit (switches 3Ć5)

To set to

Set switch 3 to

Set switch 4 to

Set switch 5 to

0

0

0

0

1

0

0

1

2

0

1

0

3

0

1

1

4

1

0

0

5

1

0

1

6

1

1

0

7

1

1

1

For example
To set the module’s DH485 station address to 15 decimal or 17 octal, set
the SW-1 switches as follows:

Set switch

To

1

0

2

1

3

1

4

1

5

1