To connect the 1785-KA5 module:

1.

Use the 3-pin port labeled Data Hwy Plus to connect the DH+
dropline (100 ft. max.) or the daisy-chained cable to the 1785-KA5
module. Connect the Allen-Bradley cable (cat. no. 1770-CD) to the
3-pin plug as shown:

Blue (2)

Shield (SH)

Clear (1)

20224

1770ĆCD

Cable

2.

Use the 9-pin D-shell port labeled Data Hwy Plus to connect your
programming terminal (such as the 1784-T50 programming terminal
used with a 1784-CP cable) to the DH+ network:

Pin

Signal

1

(clear) signal wire

5

(blue) signal wire

7

(bare) cable shield wire