Function Key

Description

[F1] Target Node

Specifies the node number of processor that is receiving the message.

[F2] Remote LINK_ID

1

Specifies the LINK_ID of the remote network where the remote target processor resides.

[F3] Remote Bridge Node Address

2

Use when the remote target device is a SLC fixed, 5/01, 5/02, or any other nonĆinternet device. The value

must be 0 anytime your remote target device is a SLC 5/03, PLCĆ5, or other internet device. Valid range is

0 - 15 decimal.

[F4] Local Address

Specifies the node address of the bridge residing on the local network that provides the link to the remote

target processor. Specifies DHĆ485 address.

[F5] File Address

For a Read (Destination) this is the address in the initiating processor which is to receive data.
For a Write (Source) this is the address in the initiating processor that is to send data.
Valid file types are S, B, T, C, R, N, I, O, M0, M1.

[F6] Target Address

For a Read (Destination) this is the address in the remote target processor that is to send data.
For a Write (Source) this is the address in the remote target processor that is to receive data.
Valid file types are S, B, T, C, R, N, I, O, M0, M1.

[F7] Message Length

Defines the length of the message in elements. One word elements are limited to a maximum length of 1

-112. Three word elements are limited to a maximum length of 1 - 37.

[F8] Message Timeout

Defines the length of the message timer in seconds. A timeout of 0 seconds means that there is no timer

and the message will wait forever for a reply. Valid range is 0 - 255 seconds.

[F10] Channel

Identifies the physical channel used for the message communication. Available channels are (0, RS232) or

(1, DH485).

1

The Remote Bridge Node Address refers to the side of the remote bridge that is connected to the local bridge's remote side. This address must be

within the range of 1 Ć 15 decimal. When this value is between 1 and 15, the MSG instruction sends gateway" packets. Gateway packets need to

contain the Remote Bridge Node Address to function. The 1785ĆKA5 module only accepts gateway packets between 1 - 15. The 5/03 MSG instruction

contains a gateway packet anytime the Remote Bridge Node Address field is nonĆzero.

2

In the cases of MSG instructions to nonĆinternet devices and end devices residing directly on the DH+ link, the Remote LINK_ID is the DH+ LINK_ID.