Communication Adapter Module

Chapter 2

2-8

Important: Each physical network link must have a unique LINK_ID
address.

The next section shows you how to mount the module in a 1771 I/O rack.
See page 2-9 for instructions on mounting the stand-alone version.

The 1785-KA5 mounts in any slot of an Allen-Bradley 1771 bulletin I/O
rack, except slot zero. If you are using a dropline/trunkline configuration,
mount the 1785-KA5 module within 10-100 feet of the DH+ trunkline. The
maximum cable length for DH485 trunk connections is 4,000 ft., with
individual stations “daisy-chained” together.

To install the 1785-KA5 module in a 1771 bulletin I/O rack:

1. Perform an orderly power down of the rack and its controlling PLC

processor.

ATTENTION: Remove system power before removing or
installing the module in the 1771 I/O chassis. Failure to observe
this warning could result in:

damage to the module’s circuitry
undesired operation and possible injury to personnel

2. Insert the optional keying bands provided with the 1771 I/O rack on

the backplane (The 1785-KA5 is keyed to protect against installing it
in the wrong I/O rack slot). Insert one band between keying positions
6 and 8. Insert the other between positions 12 and 14. The figure
below shows the keying positions:

Keying

Bands

19193

Mounting the 1785ĆKA5

Communication Adapter

Module in an I/O Rack