DH485 LINK_ID = 4

DH+ LINK_ID = 8

Installing the 1785ĆKA5

Communication Adapter Module

Chapter 2

2-7

SWĆ3: DH485 Channel LINK_ID and DH+ Channel LINK_ID

The 1785-KA5 module has two LINK_ID addresses: one for its DH485
side and one for its DH+ side. See the following table to set switches 1-8
of SW-3.

Important: Do not use a LINK_ID of 0 (zero). This address is reserved. If
you have more than one 1785-KA5 module on a single physical network,
the LINK_IDs for the two modules must be the same.

To set the DH485

LINK_ID to

Set switch 1 to Set switch 2 to Set switch 3 to Set switch 4 to

To set the DH+

LINK_ID to

Set switch 5 to Set switch 6 to Set switch 7 to Set switch 8 to

1

0

0

0

1

2

0

0

1

0

3

0

0

1

1

4

0

1

0

0

5

0

1

0

1

6

0

1

1

0

7

0

1

1

1

8

1

0

0

0

9

1

0

0

1

10

1

0

1

0

11

1

0

1

1

12

1

1

0

0

13

1

1

0

1

14

1

1

1

0

15

1

1

1

1

For example
To set the module’s DH485 LINK_ID to 4 and DH+ LINK_ID to 8, set the
switches as follows:

Set switch

To

1

0

2

1

3

0

4

0

5

1

6

0

7

0

8

0