Communicating through the 1785ĆKA5

Communication Adapter Module

Chapter 3

3-16

The monitor display screen allows you to monitor the status of the
message instruction while the processor is running:

Display Area:

Message:

Prompt:

Data/Cmd Entry:
Status:

Type:

Read/Write:

Target Device:

Channel:

F10

Target Node:

F1

Remote Bridge Link ID:

Remote Bridge Node Address:

Local Bridge Node Address:

Local/Remote:

Control Block:

Destination/Source File Address:

Target Offset

F6

Message Length in Elements:

Message Timeout (seconds):

F8

ERROR CODE:

Error Code Desc:

0

control bit address: N10 : 0/8

Peer-to-Peer

READ

485CIF

1

3

3

0

4

Remote

N10 : 0

N7 : 0

20

5

10

ignore if timed out:

continuous run:

error:

message done:

message transmitting

message enabled

to be retried:

awaiting execution:

waiting for queue space:

TO

CO

ER

DN

ST

EN

NR

EW

WQ

0

0

0

0

0

0

0

0

0

Press a function key: <ENTER> to save and exit, or <ESC> to abort

offline

no forces

INSTR INSERT

File 009

Main Functions:

F1

F6

F8

F9

TARGET

NODE

TARGET

OFFSET

MESSAGE

TIMEOUT

TOGGLE

BIT

In this screen, the 5/03 processor reads 5 elements (words)
from Target node 3 or Remote Bridge LINK_ID 3, starting at
byte offset 20 of its PLC 3 compatibility file. This is a byte
offset because the device at node 3 is a PLC-5/40.

The 5 elements are placed in the integer file starting at

error bit N10:0/12 will be set, indicating that the

instruction timed out. The device at node 3 of the
Remote Bridge LINK_ID 2 understands the
485CIF (PLC 2 emulation) protocol.

word N7:0. If 10 seconds elapse without a reply,