Assembly and Installation

Chapter 3

3Ć7

Rule 1 - Allow at least 6 vertical inches above and below all Controller
components. when more than one Controller is mounted in an enclosure, allow
at least 6 vertical inches between Controllers. Do not mount any component
above a 60

0

C air temperature level.

Rule 2 - Allow at least 4 horizontal inches on the sides of each Controller
component. when two or more Controllers are mounted in the same horizontal
plane, allow at least 6 horizontal inches between them.

Rule 3 - Allow at least 2 inches between the Controller and the wiring duct or
terminal strips.

Rule 4 - When the Power supply is mounted separately, it cannot be mounted
below the Processor.

Figure 3.5

Minimum Component Spacing Requirements (Power Supply Mounted to I/O

Chassis)