Assembly and Installation
Chapter 3
3Ć29
Figure 3.27
Field Wiring Arm/Indicator Labeling
Label for Status
Indicators
Label for Field Wiring
Arm Terminals
10844ĆI
All Low Level DC I/O lines must be properly shielded and run in a separate
duct. Serial Communication Cables may also be run with these lines.
I/O Power Cable should remain external to all wiring ducts or in a duct not
shared with other wiring within the enclosure.
1771 I/O Wiring Installation
WARNING: To avoid injury to personnel and damage to
equipment, disconnect all AC and DC power to the Controller
before attempting any wiring installation within the enclosure.
The specific wiring required for each type of I/o module is described in the
Module’s Product Data Sheet. General wiring procedures are described below.
Pivot the Field Wiring Arm up and snap it onto the wiring arm locking tab. use
Use a flat-head screwdriver to remove the terminal cover from the wiring arm to
expose the terminals. Trim the wire to the appropriate length to reach the
terminal. Strip approximately 3/8-inch of insulation from the end of the wire.