Assembly and Installation

Chapter 3

3Ć29

Figure 3.27

Field Wiring Arm/Indicator Labeling

Label for Status

Indicators

Label for Field Wiring

Arm Terminals

10844ĆI

All Low Level DC I/O lines must be properly shielded and run in a separate

duct. Serial Communication Cables may also be run with these lines.

I/O Power Cable should remain external to all wiring ducts or in a duct not

shared with other wiring within the enclosure.

1771 I/O Wiring Installation

WARNING: To avoid injury to personnel and damage to
equipment, disconnect all AC and DC power to the Controller
before attempting any wiring installation within the enclosure.

The specific wiring required for each type of I/o module is described in the
Module’s Product Data Sheet. General wiring procedures are described below.

Pivot the Field Wiring Arm up and snap it onto the wiring arm locking tab. use
Use a flat-head screwdriver to remove the terminal cover from the wiring arm to
expose the terminals. Trim the wire to the appropriate length to reach the
terminal. Strip approximately 3/8-inch of insulation from the end of the wire.