Maintenance and Troubleshooting

Chapter 5

5Ć5

Figure 5.1

Troubleshooting Flowchart

START

IF NECESSARY, DISABLE

I/O POWER, USE

EMERGENCY STOP SWITCH

REPLACE MINI-PLC-2/15

PROCESSOR RELOAD PROGRAM

IF NECESSARY AND RECHECK

CONTROLLER

REPLACE I/O POWER CABLE

RELOAD PROGRAM IF

NECESSARY RECHECK CONTROLLER

REMOVE SYSTEM POWER

REPLACE POWER SUPPLY

RELOAD PROGRAM IF

NECESSARY AND RECHECK

CONTROLLER

CORRECT LINE-VOLTAGE

RECHECK CONTROLLER

D

C

B

A

YES

NO

YES

NO

YES

YES

NO

NO

NO

YES

NO

YES

YES

NO

10138-I

CONTROLLED IN RUN OR RUN/PROG

MODE OUTPUTS DO NOT BEHAVE AS

PROGRAMMED

IS

LINEĆVOLTAGE

WITHIN NORMAL

RANGE?

IS

RUN

INDICATOR

ON?

IS

PROCESSOR

INDICATOR

ON?

IS

MEMORY

INDICATOR

ON?

ARE

PWER SUPPLY

OUTPUT VOLTAGES

CORRECT?

ARE

VOLATAGES

THROUGH I/O

POWER CABLE

CORRECT?

IS

DC ON

INDICATOR

ON?