Assembly and Installation

Chapter 3

3Ć26

Figure 3.24

Attaching Filed Wiring Arms

Wiring Arm

Horizontal Bar

Remove

Install

CĆShaped

Bracket

10842ĆI

Field Wiring Considerations

When planning duct layout, the following categories of wires and cables
associated with an A-B Programmable Controller should be considered:

I/O Power Cable carries regulated 5V to the Processor and the I/O Rack.

Data Highway Cables (Serial Communication) carry data transmissions

between Processors and/or Computers.

Low Level DC I/O lines carry low voltage low per signals and their input

circuits have short time constant filters so that short pulses can be detected.
Low Level DC I/O lines connect TTL, Analog, Encoder/Counter, Pulse
Output, Fast Response, Thermocouple and other Low Level DC I/O
Modules.

AC I/O lines and High Level DC I/O lines have a greater degree of noise

immunity than Low Level DC I/O lines.